Ask Latest Price
Video Channel
Brand Name :Honeywell
Model Number :10205/2/1
Place of Origin :USA
MOQ :1pc
Price :$1000
Payment Terms :T/T
Supply Ability :999pcs
Delivery Time :5-7days
Packaging Details :New and original factory, individual box packing
Name :Honeywell 10205/2/1 Fail-Safe Analog Output Module
Product ID :10205/2/1
Product Net Length :350mm
Product Net Width :120mm
Product Net Height :50mm
Condition :New
Warranty :1 year
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Honeywell 10205/2/1 Fail-Safe Analog Output Module

Honeywell 10205/2/1 Fail-Safe Analog Output Module.pdf

Product Details:

The fail-safe analog output module 10205/2/1 has two 0(4)-20 mA output channels for analog control applications.

The load may only be resistive or capacitive. Inductive loads will cause the analog output module to be reported faulty. The two analog outputs are galvanically isolated from the 24 Vdc and the 5 Vdc.

The 0 V 1 and 0 V 2 pins are interconnected on the module. Each analog output channel consists of a 12-bit D/A converter for the output value and an A/D converter which reads the output value. Using the A/D converter it is possible to check the correct functioning of the D/A converter. Within the configured process safety time, the analog outputs are tested for:

• correct output value (current value ± 5%),

• ability to de-energize, and

• crosstalk between analog outputs.

If I/O backplanes are used, the analog output module 10205/2/1 requires a 10205/A/. module on each channel. Each analog output has a secondary means of de-energization, which enables the watchdog and/or the processor to de-energize the outputs, irrespective of the result of the application value.

The analog output module 10205/2/1 can only be used in non-redundant I/O configurations as it is not possible to put current outputs in parallel (which would be required for redundant I/O configurations).

Honeywell 10205/2/1 Fail-Safe Analog Output Module