F3330 HIMA PLC 8 Channel Analog Fold Output Module Safety Related Digital

Ask Latest Price
Video Channel
Brand Name :HIMA
Model Number :F3330
Place of Origin :Germany
MOQ :1pc
Price :$2000
Payment Terms :T/T
Supply Ability :999pcs
Delivery Time :5-7days
Packaging Details :New and original factory, individual box packing
Name :F3330 8 fold output module safety related HIMA PLC
Product ID :F3330
Manufacture :HIMA
Product Type :8-Channel Output Module
Condition :100% New
Warranty :1year
Shipping term :TNT, DHL, UPS DHL TNT EMS Fed, FedEx, EMS..
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

F3330 8 fold output module safety related HIMA PLC

Product Details:

F3330: 8 fold output module, safety related resistive load or inductive load up to 500 mA (12 W),

lamp connection up to 4 W, with integrated safety shutdown, with safe isolation,

no output signal with break of the L- supply requirement class AK 1 ... 6

The module is automatically tested during operation. The main test routines are: – Reading back of the output signals.

The operating point of the 0 signal read back is ≤ 6.5 V. Up to this value the level of the 0 signal may arise

in case of a fault and this will not be detected – Switching capability of test signal and cross-talking (walking-bit test).

  • Outputs 500 mA, k short circuit proof
  • Internal voltage drop max. 2 V at 500 mA load
  • Admissible line resistance (in + out) max. 11 Ohm
  • Undervoltage tripping at ≤ 16 V
  • Operating point for short circuit current 0.75 ... 1.5 A
  • Outp. leakage current max. 350 µA
  • Output voltage if output is reset max. 1,5 V
  • Duration of the test signal max. 200 µs
  • Space requirement 4 TE
  • Operating data 5 V DC: 110 mA
  • 24 V DC: 180 mA in add. load

F3330 HIMA PLC 8 Channel Analog Fold Output Module Safety Related Digital